Engineering data

REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Dry Cooler capacaties are tested according to EN 1048.
2. Ratings shown are for clean tubes with 34% ethylene glycol solution by volume, 40°C in and 35°C out, 25°C ambient air temperature.
3. Sound Pressure Levels (LpA) are measured in the horizontal plane at a distance of 10 m from the connection end of the unit, under free field conditions.

Last update: 19/04/2019

DFCV S91XX

DFCV_engineering_data

Model Nr. of Fans Nominal Capacity (kW) Air Flow (m³/s) Cooling Agent l/s Δp kPa Tube Internal Volume (dm³) Surface (m²) Connections Ship. Weight(kg) LpA dB(A) Dimensions (mm)
Δ /ϒ Δ /ϒ Δ /ϒ Δ /ϒ Δ /ϒ L W H
S9122-L616D 4 (2+2) 366/291 26,4/19,7 19,3/15,3 31/21 287 1335 4 x ND80 1606 58/52 2517 2400 2810
S9123-S616D 6 (3+3) 555/436 39,6/29,6 29,3/23,0 36/23 430 2002 8 x ND80 2120 60/54 3617 2400 2810
S9124-M616D 8 (4+4) 732/582 52,8/39,5 38,6/30,7 29/19 574 2669 8 x ND80 3015 61/55 4717 2400 2810
S9125-M616D 10 (5+5) 937/733 66,0/49,4 49,5/38,7 50/32 717 3336 8 x ND100 3699 62/56 5817 2400 2810
S9126-D616D 12 (6+6) 1110/873 79,2/59,3 58,6/46,1 41/26 860 4004 8 x ND100 4262 63/57 6917 2400 2810